#Heat pump and hot water behind a gateway

In many buildings, the heat pump, the hot-water tank, and the floor heating are controlled by their own system, connected to KNX through a gateway (Modbus, BACnet, or M-Bus). KNX then sees only the values and commands that the gateway exchanges. The diagram shows that boundary; the other system is not simulated.

The line shows its power supply (640 mA) next to its name.

<bus-diagram>
<script type="application/json">
{
  "formatVersion": 2,
  "title": "Heat pump and hot water behind a gateway",
  "description": "The heat pump and the hot-water tank are controlled by their own system, linked to KNX by a Modbus gateway. Enter the tank, flow, and return temperatures on the gateway: they are sent on KNX and shown on the display. The keys select the heating mode and request a hot-water boost; the gateway forwards these commands to Modbus, which is not simulated. The energy meter measures the heat pump in kW and kWh and the water heater in W and Wh; enter a measured power to change it.",
  "lines": [{ "address": "1.1", "name": "Plant room", "powerSupply": { "currentMa": 640 } }],
  "groupAddresses": [
    { "address": "3/1/0", "name": "Hot-water tank temperature", "dpt": "9.001" },
    { "address": "3/1/1", "name": "Heating flow temperature", "dpt": "9.001" },
    { "address": "3/1/2", "name": "Heating return temperature", "dpt": "9.001" },
    { "address": "3/2/0", "name": "Heating mode", "dpt": "20.102" },
    { "address": "3/2/1", "name": "Hot-water boost", "dpt": "1.001" },
    { "address": "9/0/1", "name": "Heat pump power", "dpt": "9.024" },
    { "address": "9/1/1", "name": "Heat pump energy", "dpt": "13.013" },
    { "address": "9/0/2", "name": "Water heater power", "dpt": "14.056" },
    { "address": "9/1/2", "name": "Water heater energy", "dpt": "13.010" }
  ],
  "devices": [
    {
      "id": "keys",
      "name": "Plant room keys",
      "address": "1.1.1",
      "kind": "pushButton",
      "behavior": "pushButton/v1",
      "objects": [
        {
          "id": "mode",
          "name": "Heating mode",
          "ga": "3/2/0",
          "dpt": "20.102",
          "port": "input",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "boost",
          "name": "Hot-water boost",
          "ga": "3/2/1",
          "dpt": "1.001",
          "port": "input",
          "flags": { "W": false, "T": true }
        }
      ],
      "buttons": [
        { "id": "comfort", "label": "Comfort", "press": { "object": "mode", "value": 1 } },
        { "id": "economy", "label": "Economy", "press": { "object": "mode", "value": 3 } },
        {
          "id": "boostKey",
          "label": "Hot-water boost",
          "press": { "object": "boost", "value": "toggle" },
          "led": "boost"
        }
      ]
    },
    {
      "id": "gateway",
      "name": "Heat pump gateway",
      "address": "1.1.10",
      "kind": "gateway",
      "behavior": "systemGateway/v1",
      "objects": [
        {
          "id": "tank",
          "name": "Tank temperature",
          "ga": "3/1/0",
          "dpt": "9.001",
          "port": "value",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "flow",
          "name": "Flow temperature",
          "ga": "3/1/1",
          "dpt": "9.001",
          "port": "value",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "return",
          "name": "Return temperature",
          "ga": "3/1/2",
          "dpt": "9.001",
          "port": "value",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "mode",
          "name": "Heating mode",
          "ga": "3/2/0",
          "dpt": "20.102",
          "port": "command",
          "flags": { "W": true, "T": false }
        },
        {
          "id": "boost",
          "name": "Hot-water boost",
          "ga": "3/2/1",
          "dpt": "1.001",
          "port": "command",
          "flags": { "W": true, "T": false }
        }
      ],
      "inputs": [
        {
          "id": "tank",
          "type": "number",
          "label": "Tank (°C)",
          "object": "tank",
          "min": 10,
          "max": 80,
          "step": 1
        },
        {
          "id": "flow",
          "type": "number",
          "label": "Flow (°C)",
          "object": "flow",
          "min": 20,
          "max": 60,
          "step": 1
        },
        {
          "id": "return",
          "type": "number",
          "label": "Return (°C)",
          "object": "return",
          "min": 15,
          "max": 50,
          "step": 1
        }
      ]
    },
    {
      "id": "meter",
      "name": "Energy meter",
      "address": "1.1.11",
      "kind": "energyMeter",
      "behavior": "energyMeter/v1",
      "objects": [
        {
          "id": "hpPower",
          "name": "Heat pump power",
          "ga": "9/0/1",
          "dpt": "9.024",
          "port": "power",
          "channel": "hp",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "hpEnergy",
          "name": "Heat pump energy",
          "ga": "9/1/1",
          "dpt": "13.013",
          "port": "energy",
          "channel": "hp",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "whPower",
          "name": "Water heater power",
          "ga": "9/0/2",
          "dpt": "14.056",
          "port": "power",
          "channel": "wh",
          "flags": { "W": false, "T": true }
        },
        {
          "id": "whEnergy",
          "name": "Water heater energy",
          "ga": "9/1/2",
          "dpt": "13.010",
          "port": "energy",
          "channel": "wh",
          "flags": { "W": false, "T": true }
        }
      ],
      "inputs": [
        {
          "id": "hp",
          "type": "number",
          "label": "Heat pump (kW)",
          "object": "hpPower",
          "min": 0,
          "max": 6,
          "step": 0.1
        },
        {
          "id": "wh",
          "type": "number",
          "label": "Water heater (W)",
          "object": "whPower",
          "min": 0,
          "max": 3000,
          "step": 100
        }
      ],
      "channels": [
        {
          "id": "hp",
          "label": "Heat pump",
          "initialState": { "powerW": 1800, "energyWh": 4210000 },
          "equipment": null
        },
        { "id": "wh", "label": "Water heater", "equipment": null }
      ]
    },
    {
      "id": "display",
      "name": "Plant room display",
      "address": "1.1.20",
      "kind": "display",
      "behavior": "display/v1",
      "objects": [
        {
          "id": "tank",
          "name": "Hot-water tank",
          "ga": "3/1/0",
          "dpt": "9.001",
          "port": "display",
          "flags": { "W": true, "T": false }
        },
        {
          "id": "flow",
          "name": "Flow",
          "ga": "3/1/1",
          "dpt": "9.001",
          "port": "display",
          "flags": { "W": true, "T": false }
        },
        {
          "id": "return",
          "name": "Return",
          "ga": "3/1/2",
          "dpt": "9.001",
          "port": "display",
          "flags": { "W": true, "T": false }
        },
        {
          "id": "hpPower",
          "name": "Heat pump",
          "ga": "9/0/1",
          "dpt": "9.024",
          "port": "display",
          "flags": { "W": true, "T": false }
        },
        {
          "id": "hpEnergy",
          "name": "Heat pump energy",
          "ga": "9/1/1",
          "dpt": "13.013",
          "port": "display",
          "flags": { "W": true, "T": false }
        },
        {
          "id": "whPower",
          "name": "Water heater",
          "ga": "9/0/2",
          "dpt": "14.056",
          "port": "display",
          "flags": { "W": true, "T": false }
        }
      ]
    }
  ],
  "options": { "speed": 1, "filterTables": false }
}
</script>
</bus-diagram>