These tables are generated from registered definitions. An extension can register additional behaviors or equipment; see the extension guide.

#Behaviors

#pushButton/v1

Push button or sensor: each gesture writes a value into a local object, then transmits it. Uses buttons and inputs.

Ports

Port DPT Channel Role
input any none object sent by a key or input
display any none object receiving a value (indicator or feedback)

Device parameters (parameters)

Parameter Type Default Constraints Description
longPressMs integer 500 ≥ 100 ; ≤ 10000 Press duration that counts as a long press (ms), for keys with short and long actions.

#switchActuator/v1

Switch actuator: each channel drives a relay; optional timer, status feedback, and power and energy metering. Output command: switch.

Ports

Port DPT Channel Role
switch 1.001 required Channel switch command (0 = off, 1 = on).
status 1.001 required Relay status feedback, sent after each effective change.
scene 17.001 optional (all channels when omitted) Scene number (bus byte 0–63 represents scenes 1–64); without a channel, apply to all channels.
forced 2.001 required Priority override (2 = force off, 3 = force on, 0/1 = end override).
power 14.056, 9.024 required electrical power drawn by the load of the channel: W with 14.056, kW with 9.024
energy 13.010, 13.013 required active energy counted for the channel, sent cyclically: Wh with 13.010, kWh with 13.013
totalPower 14.056, 9.024 none sum of the power of all channels: W with 14.056, kW with 9.024
powerLimit 1.005, 1.001 none 1 when the total power reaches powerLimitW, 0 after hysteresis (load shedding)

Device parameters (parameters)

Parameter Type Default Constraints Description
meterIntervalMs integer 5000 ≥ 1000 Cyclic sending of power and energy values (ms), for channels with metering objects.
powerSendDeltaW number 10 ≥ 0 Send a power value when it changes by at least this many watts.
energyTimeScale number 60 > 0 Energy counting speed: 60 counts one simulated second as one minute, so that the counter moves visibly; 1 counts real time.
powerLimitW number 0 ≥ 0 Total power (W) of the actuator outputs at which the powerLimit object is set, for load shedding (0 disables it).
sheddingTimeMs integer 20000 ≥ 0 A shed output is switched on again after this time, if its command still requests it; it is shed again if the limit is still exceeded.
powerLimitHysteresisW number 50 ≥ 0 The powerLimit object is reset below limit − hysteresis (W).

Channel parameters (channels[].parameters)

Parameter Type Default Constraints Description
timerMs integer null null > 0
timerRetrigger string "restart" "restart" (Restarts), "none" (No effect), "add" (Extends) When 1 is received during a timer: restart begins a full period, none ignores it, and add extends the period (up to five times).
timerWarningMs integer 0 ≥ 0 Time before the timer ends when the output briefly opens for one second as a warning (0 disables the warning).
timerOffAllowed boolean true Allow a 0 write to switch off before the timer ends; otherwise ignore it.
loadShedding boolean false Switch this output off while the total power limit of the actuator is exceeded (load shedding).
relayMode string "normallyOpen" "normallyOpen" (Normally open), "normallyClosed" (Normally closed) normallyOpen closes the contact when the channel is on; normallyClosed closes it when the channel is off, so the load is powered while the switching state is 0. Status feedback reports the switching state, not the contact.
statusDelayMs integer 300 ≥ 0 Delay before sending status feedback (ms).
afterForcing string "lastCommand" "lastCommand" (Last command), "previous" (Previous state), "unchanged" (Unchanged), "on" (Start), "off" (Stop), "toggle" (Toggle) State after a priority override ends: follow the latest command received during the override, restore the previous state, keep the forced state, switch on, switch off, or invert the forced state.

Initial channel state (channels[].initialState)

Parameter Type Default Constraints Description
on boolean false Switching state of the channel when the simulation starts.

#shutterActuator/v1

Shutter actuator without sensor: position estimated from the configured travel time. Output command: motor.

Ports

Port DPT Channel Role
move 1.008 required Shutter: 0 raises toward 0%, 1 lowers toward 100%.
stopStep 1.007 required Shutter: stop when moving; otherwise step by stepPct (0 up, 1 down).
positionCommand 5.001 required Shutter target position in percent.
positionStatus 5.001 required Actuator's estimated shutter position, sent after stopping.
scene 17.001 optional (all channels when omitted) Scene number (bus byte 0–63 represents scenes 1–64); without a channel, apply to all channels.
slatCommand 5.001 required slat angle (0 % open, 100 % closed) of a venetian blind
slatStatus 5.001 required estimated slat angle, sent after stopping
windAlarm 1.005, 1.001 optional (all channels when omitted) 1 raises the shutter and locks it against other commands; 0 releases it in place

Channel parameters (channels[].parameters)

Parameter Type Default Constraints Description
estimatedTravelTimeMs (required) integer > 0 Travel time configured in the actuator (ms): downwards, and upwards unless estimatedTravelTimeUpMs is set.
estimatedTravelTimeUpMs integer > 0 Upward travel time configured in the actuator (ms), when it differs from the downward time; many actuators take separate times because a shutter rises more slowly than it falls.
startDelayMs integer 300 ≥ 0 Delay before starting or reversing motion (ms).
statusDelayMs integer 300 ≥ 0 Delay before sending position feedback (ms).
slatTravelMs integer 0 ≥ 0 Venetian blind: time configured for the slats to turn from open to closed (ms). A movement first turns the slats; a short press at rest turns them by slatStepPct. 0 for a roller shutter without slats.
slatStepPct number 20 ≥ 1 ; ≤ 100 Slat angle change for a short press at rest (%).
stepPct number 0 ≥ 0 ; ≤ 100 Position step for a stop/step command received at rest by a shutter without slats (%). 0 (default): no movement, as in the KNX stop/step function, where the step turns slats; some actuators move a roller shutter by this amount instead.
endSupplementPct number 0 ≥ 0 ; ≤ 50 Extra travel time toward 0% or 100%, as a percentage of full travel. The motor runs even if the estimate is already at the limit; the end stop recalibrates the estimate (often 5–10% on a real actuator).
invertOutput boolean false Invert the up and down outputs to compensate a motor wired in reverse (shutter parameter wiringReversed). Without such wiring, enabling it makes the shutter move opposite to the commands.

Initial channel state (channels[].initialState)

Parameter Type Default Constraints Description
estimatedPositionPct number 0 ≥ 0 ; ≤ 100 Position the actuator assumes at start (0 = fully open, 100 = fully closed); the connected shutter starts at its own position.
estimatedSlatPct number 0 ≥ 0 ; ≤ 100 Slat angle the actuator assumes at start (venetian blinds).

#display/v1

Display / supervisor: receives and shows values, with no output or retransmission.

Ports

Port DPT Channel Role
display any none Object that receives and displays a value, such as an indicator or supervisor.

No parameters.

#passive/v1

Device without logic: it only keeps the values of its objects.

Ports

Port DPT Channel Role
input any none Object written by a button or numeric input, then transmitted.
display any none Object that receives and displays a value, such as an indicator or supervisor.

No parameters.

#presenceDetector/v1

Presence detector: sends 1 on first detection, 0 when its hold time ends (restarted by each detection). Uses buttons and inputs.

Ports

Port DPT Channel Role
input 1.001, 1.018 none output object: 1 on detection, 0 when the timer expires
brightness 9.004 none measured brightness (lx), entered by the reader and sent; there is no light model

Device parameters (parameters)

Parameter Type Default Constraints Description
holdMs integer 10000 > 0 Time with no detected presence before sending 0 (ms); restarted on each detection.
retrigger boolean true Each activation restarts the timer; otherwise it runs from the first activation.
sendOnEnd boolean true Send 0 when the timer expires; otherwise the detector sends only 1 and the actuator handles switch-off.
brightnessThresholdLux number 0 ≥ 0 A detection switches on only while the entered brightness is below this value (lx); an active presence is still extended. 0 disables the threshold.

#usbInterface/v1

USB interface: writes and reads group addresses from the USB interface panel of the diagram.

Ports

Port DPT Channel Role

Device parameters (parameters)

Parameter Type Default Constraints Description
groupAddresses string "" Group addresses assigned to this interface in the project, separated by spaces or commas. Coupler filter tables include them, so telegrams on these addresses cross couplers to and from the interface. Without them, a coupler filters an address that is not used on the interface side.

#dimmerActuator/v1

Dimmer: switching, relative (3.007) and absolute (5.001) dimming, tunable white (7.600), status feedback. Output command: dim.

Ports

Port DPT Channel Role
switch 1.001 required Channel switch command (0 = off, 1 = on).
dim 3.007 required Relative dimming (3.007): direction bit and step size 1–7; 0 stops dimming.
value 5.001 required Brightness value in percent (5.001); zero switches off.
status 1.001 required Relay status feedback, sent after each effective change.
valueStatus 5.001 required Brightness value feedback (5.001), sent after a transition.
scene 17.001 optional (all channels when omitted) Scene number (bus byte 0–63 represents scenes 1–64); without a channel, apply to all channels.
colourTemperature 7.600 required colour temperature setpoint (K) of a tunable white channel
colourTemperatureStatus 7.600 required applied colour temperature (K)

Channel parameters (channels[].parameters)

Parameter Type Default Constraints Description
onLevel string "fixed" "fixed" (Set value), "last" (Last value) Level when switched on: fixed uses onLevelPct; last restores the level before switch-off.
onLevelPct number 100 ≥ 1 ; ≤ 100 Level reached when a value of 1 is received (fixed mode).
dimTimeMs integer 5000 > 0 Time for a 0–100% relative dimming transition (DPT 3.007); smaller steps take less time.
switchFadeMs integer 0 ≥ 0 Transition time when switching on or off (0 means immediate).
valueFadeMs integer 0 ≥ 0 Transition time to a received value (5.001) or scene preset.
minLevelPct number 1 ≥ 0 ; ≤ 50 Minimum relative dimming level.
maxLevelPct number 100 ≥ 50 ; ≤ 100 Upper limit for relative dimming and received values.
dimSwitchesOn boolean true An increase command turns on a channel that is off.
dimSwitchesOff boolean false A decrease command may dim to off; otherwise it stops at the minimum level.
valueSwitchesOn boolean true A brightness value above 0 turns on a channel that is off; otherwise the value is ignored while the channel is off.
valueSwitchesOff boolean true A brightness value of 0 turns the channel off; otherwise the channel dims to its minimum level.
statusDelayMs integer 300 ≥ 0 Delay before sending status feedback (ms), after a transition completes.
minColourK integer 2700 ≥ 1000 ; ≤ 10000 Lowest colour temperature (K) of a tunable white channel; lower requests are limited to it.
maxColourK integer 6500 ≥ 1000 ; ≤ 10000 Highest colour temperature (K) of a tunable white channel; higher requests are limited to it.

Initial channel state (channels[].initialState)

Parameter Type Default Constraints Description
levelPct number 0 ≥ 0 ; ≤ 100 Level of the output when the simulation starts; 0 is off.
colourTemperatureK integer 4000 ≥ 1000 ; ≤ 10000 Colour temperature (K) at start, for a channel with a colourTemperature object.

#daliGateway/v1

KNX/DALI gateway: each channel is a DALI group of ballasts; broadcast, scenes and fault reporting. Output command: dim.

Ports

Port DPT Channel Role
switch 1.001 required Channel switch command (0 = off, 1 = on).
dim 3.007 required Relative dimming (3.007): direction bit and step size 1–7; 0 stops dimming.
value 5.001 required Brightness value in percent (5.001); zero switches off.
status 1.001 required Relay status feedback, sent after each effective change.
valueStatus 5.001 required Brightness value feedback (5.001), sent after a transition.
scene 17.001 optional (all channels when omitted) Scene number (bus byte 0–63 represents scenes 1–64); without a channel, apply to all channels.
error 1.005 required lamp or ballast fault in the group
broadcastSwitch 1.001 none Switch all groups with a DALI broadcast.
broadcastValue 5.001 none Set all group levels with a DALI broadcast.
generalError 1.005 none Fault on the DALI line across all groups (1.005).

Device parameters (parameters)

Parameter Type Default Constraints Description
pollMs integer 2000 ≥ 500 Interval between ballast status polls for faults.

Channel parameters (channels[].parameters)

Parameter Type Default Constraints Description
onLevel string "fixed" "fixed" (Set value), "last" (Last value) Level when switched on: fixed uses onLevelPct; last restores the level before switch-off.
onLevelPct number 100 ≥ 1 ; ≤ 100 Level reached when a value of 1 is received (fixed mode).
dimTimeMs integer 5000 > 0 Time for a 0–100% relative dimming transition (DPT 3.007); smaller steps take less time.
switchFadeMs integer 0 ≥ 0 Transition time when switching on or off (0 means immediate).
valueFadeMs integer 0 ≥ 0 Transition time to a received value (5.001) or scene preset.
minLevelPct number 1 ≥ 0 ; ≤ 50 Minimum relative dimming level.
maxLevelPct number 100 ≥ 50 ; ≤ 100 Upper limit for relative dimming and received values.
dimSwitchesOn boolean true An increase command turns on a channel that is off.
dimSwitchesOff boolean false A decrease command may dim to off; otherwise it stops at the minimum level.
valueSwitchesOn boolean true A brightness value above 0 turns on a channel that is off; otherwise the value is ignored while the channel is off.
valueSwitchesOff boolean true A brightness value of 0 turns the channel off; otherwise the channel dims to its minimum level.
statusDelayMs integer 300 ≥ 0 Delay before sending status feedback (ms), after a transition completes.
minColourK integer 2700 ≥ 1000 ; ≤ 10000 Lowest colour temperature (K) of a tunable white channel; lower requests are limited to it.
maxColourK integer 6500 ≥ 1000 ; ≤ 10000 Highest colour temperature (K) of a tunable white channel; higher requests are limited to it.

Initial channel state (channels[].initialState)

Parameter Type Default Constraints Description
levelPct number 0 ≥ 0 ; ≤ 100 Level of the output when the simulation starts; 0 is off.
colourTemperatureK integer 4000 ≥ 1000 ; ≤ 10000 Colour temperature (K) at start, for a channel with a colourTemperature object.

#roomThermostat/v1

Room thermostat: comfort / standby / economy / protection modes (20.102), window and presence, PI control (5.001 or PWM) or two-point, heating and cooling. Uses buttons and inputs.

Ports

Port DPT Channel Role
actualTemp 9.001 none Thermostat: measured temperature (9.001), sent on change.
externalTemp 9.001 none replaces the internal sensor after a value is received
baseSetpoint 9.001 none Thermostat: base heating comfort setpoint (9.001).
setpointShift 9.002 none base setpoint = configured setpoint + offset
setpointStatus 9.001 none Thermostat: current setpoint (9.001).
hvacMode 20.102 none Thermostat: selected mode (20.102: 0 auto, 1 comfort, 2 standby, 3 economy, 4 protection).
hvacModeStatus 20.102 none Thermostat: current mode (20.102).
presence 1.018, 1.001 none 1 = presence: comfort mode
window 1.019, 1.001, 1.009 none open window (1.019 / 1.001: 1 = open; 1.009: 0 = open): protection mode, highest priority
heatCool 1.100 none 1 = heating, 0 = cooling
heatCoolStatus 1.100 none Thermostat: current heating or cooling mode.
heatingValue 5.001 none continuous control value from 0 to 100%
heatingSwitch 1.001 none two-point control, or PWM under PI control
coolingValue 5.001 none Thermostat: continuous cooling control value (5.001).
coolingSwitch 1.001 none Thermostat: one-bit cooling command.

Device parameters (parameters)

Parameter Type Default Constraints Description
controlType string "pi" "pi" (PI (continuous or PWM)), "twoPoint" (Two-point) pi uses proportional-integral control with a continuous value (5.001) or PWM (1 bit); twoPoint uses on/off control with hysteresis.
comfortC number 21 ≥ 5 ; ≤ 35 Initial heating comfort setpoint (°C); the baseSetpoint object can replace it.
standbyShiftK number 2 ≥ 0 ; ≤ 10 Standby setpoint offset (K): lower for heating, higher for cooling.
economyShiftK number 4 ≥ 0 ; ≤ 15 Economy or night setpoint offset (K): lower for heating, higher for cooling.
frostProtectionC number 7 ≥ 3 ; ≤ 15 Heating setpoint in protection mode (°C).
heatProtectionC number 35 ≥ 25 ; ≤ 45 Cooling setpoint in protection mode (°C).
deadZoneK number 3 ≥ 0 ; ≤ 10 Difference between heating and cooling comfort setpoints (K), for example 21 °C and 24 °C.
minSetpointC number 5 ≥ 0 ; ≤ 30 Lowest base setpoint accepted (°C); lower received or entered values are raised to it.
maxSetpointC number 35 ≥ 10 ; ≤ 50 Highest base setpoint accepted (°C); higher received or entered values are lowered to it.
hysteresisK number 0.5 ≥ 0.1 ; ≤ 5 Two-point control switches on again when temperature differs from the setpoint by this amount (K).
proportionalBandK number 2 ≥ 0.5 ; ≤ 10 Temperature difference (K) that produces 100% output from the proportional term.
integralTimeMs integer 120000 ≥ 0 PI integral time: a constant error doubles the proportional response after this duration (0 selects P control). Real installations use 60–240 minutes; the default follows compressed simulated room time.
pwmCycleMs integer 20000 ≥ 1000 PWM cycle period for a 1-bit control object (real installations typically use 10–20 minutes).
controlPeriodMs integer 1000 ≥ 100 Interval at which the controller recalculates its control value from the measured temperature.
valueSendDeltaPct number 5 ≥ 1 ; ≤ 50 Send the control value when it changes by at least this many percentage points.
externalTempTimeoutMs integer 0 ≥ 0 If no externalTemp value arrives within this time, control uses the internal sensor again until a new value arrives (0 disables monitoring).
valueCyclicMs integer 0 ≥ 0 Periodically resend the control value (0 disables it); needed when the actuator monitors incoming values.
temperatureSendDeltaK number 0.2 ≥ 0.1 ; ≤ 5 Send measured temperature when it changes by at least this amount (K).
temperatureCyclicMs integer 0 ≥ 0 Also send the measured temperature at this interval, even without change; 0 disables cyclic sending.

#heatingActuator/v1

Heating actuator: each output drives an electrothermal valve; continuous control value (5.001) converted to PWM, or direct 1-bit command, monitoring and emergency mode. Output command: switch.

Ports

Port DPT Channel Role
value 5.001 required Brightness value in percent (5.001); zero switches off.
switch 1.001 required two-point or thermostat PWM control
valueStatus 5.001 required Brightness value feedback (5.001), sent after a transition.
fault 1.005 required missing control value: fallback program

Channel parameters (channels[].parameters)

Parameter Type Default Constraints Description
valveType string "normallyClosed" "normallyClosed" (Closed when de-energised), "normallyOpen" (Open when de-energised) normallyClosed: valve closed without power (common); normallyOpen: valve open without power, so the output is inverted.
cycleMs integer 20000 ≥ 1000 PWM period for a continuous control value: powered time equals value × period (real installations typically use 10–20 minutes).
monitoringMs integer 0 ≥ 0 If no control value arrives within this time, enter fallback mode and report a fault (0 disables monitoring).
emergencyPct number 30 ≥ 0 ; ≤ 100 Control value applied in fallback mode.

#windowContact/v1

Window contact (binary input): sends the opening and closing of its room's window.

Ports

Port DPT Channel Role
contact 1.019, 1.001, 1.009 none 1.019 / 1.001: 1 means open; 1.009: 1 means closed

Device parameters (parameters)

Parameter Type Default Constraints Description
contactType string "normallyOpen" "normallyOpen" (Normally open), "normallyClosed" (Normally closed) Physical contact: a normally open contact is closed while the window is closed; a normally closed contact is open while the window is closed.
invert boolean false Interpret the electrical input for a normally closed contact. The transmitted value always follows the DPT (1.019: 1 = open; 1.009: 1 = closed).
sendOnStart boolean true Send contact state when the simulation starts, as after bus power returns, so a thermostat can detect an already open window.
startDelayMs integer 1000 ≥ 0 Delay after the simulation starts before the contact state is sent.

#temperatureSensor/v1

Room temperature sensor: sends its room's temperature on change and cyclically.

Ports

Port DPT Channel Role
temperature 9.001 none Sensor: room temperature (9.001).

Device parameters (parameters)

Parameter Type Default Constraints Description
sendDeltaK number 0.2 ≥ 0.1 ; ≤ 5 Temperature change (K) that triggers a transmission.
cyclicMs integer 0 ≥ 0 Periodic retransmission (0 disables it).

#logicGate/v1

Logic module: combines one-bit inputs (AND, OR, XOR, NOT) and sends the result; an optional enable object blocks the output.

Ports

Port DPT Channel Role
logicIn 1.001, 1.002, 1.003, 1.005, 1.018, 1.019 none one-bit input of the logic function
enable 1.003, 1.001 none 0 blocks the output; 1 enables it again and sends the current result
time 10.001 none time received from a clock master, used by the time window
logicOut 1.001, 1.002, 1.003, 1.005, 1.008, 1.009 none result of the logic function

Device parameters (parameters)

Parameter Type Default Constraints Description
operation string "and" "and" (AND), "or" (OR), "xor" (XOR), "not" (NOT (first input)) Logic function applied to the inputs; an input with no value yet counts as 0.
activeFrom string "" Start of a daily time window (HH:MM). With activeTo and a time object, the output is 1 only inside the window; the window may cross midnight.
activeTo string "" End of the daily time window (HH:MM), excluded.
sendOnChangeOnly boolean true Send the result only when it differs from the last transmitted value.

#weatherStation/v1

Weather station: sends measured wind speed, brightness, and temperature; sets one-bit outputs when wind or brightness thresholds are reached. Uses buttons and inputs.

Ports

Port DPT Channel Role
wind 9.005, 9.028 none measured wind speed, sent when entered: m/s with 9.005, km/h with 9.028 (thresholds stay in m/s)
brightness 9.004 none measured brightness (lux), sent when entered
outdoorTemp 9.001 none measured outdoor temperature (°C), sent when entered
windAlarm 1.005, 1.001 none 1 when the wind threshold is reached, 0 after hysteresis
sunProtection 1.001, 1.002 none 1 when the brightness threshold is reached, 0 after hysteresis

Device parameters (parameters)

Parameter Type Default Constraints Description
windThreshold number 10 ≥ 0 Wind speed (m/s) at which the wind alarm is set.
windHysteresis number 2 ≥ 0 The alarm is reset when the wind speed falls below threshold − hysteresis (m/s).
brightnessThreshold number 40000 ≥ 0 Brightness (lux) at which sun protection is requested.
setsRoomOutdoorTemperature boolean true An entered outdoor temperature also becomes the outdoor temperature of every room in the thermal model, so that the building reacts to it.
brightnessHysteresis number 5000 ≥ 0 The request is reset when brightness falls below threshold − hysteresis (lux).

#airQualitySensor/v1

Air quality sensor: sends measured temperature, relative humidity, and CO₂; sets alarms at thresholds and controls ventilation in three steps. Uses buttons and inputs.

Ports

Port DPT Channel Role
temperature 9.001 none measured temperature (°C), sent when entered
humidity 9.007, 5.001 none measured relative humidity (%), sent when entered: 2-byte float with 9.007, one byte with 5.001
co2 9.008 none measured CO₂ concentration (ppm), sent when entered
co2Alarm 1.005, 1.001 none 1 when the CO₂ alarm threshold is reached, 0 after hysteresis
humidityAlarm 1.005, 1.001 none 1 when the humidity alarm threshold is reached, 0 after hysteresis
ventilation 5.001 none control value (%) of the current ventilation step

Device parameters (parameters)

Parameter Type Default Constraints Description
co2AlarmPpm number 1500 ≥ 0 ; ≤ 10000 CO₂ concentration (ppm) at which the CO₂ alarm is set.
co2AlarmHysteresisPpm number 100 ≥ 0 ; ≤ 10000 The CO₂ alarm is reset below threshold − hysteresis (ppm).
humidityAlarmPct number 70 ≥ 0 ; ≤ 100 Relative humidity (%) at which the humidity alarm is set.
humidityAlarmHysteresisPct number 5 ≥ 0 ; ≤ 100 The humidity alarm is reset below threshold − hysteresis (%).
step1Ppm number 800 ≥ 0 ; ≤ 10000 CO₂ concentration (ppm) between ventilation steps 0 and 1.
step2Ppm number 1000 ≥ 0 ; ≤ 10000 CO₂ concentration (ppm) between ventilation steps 1 and 2.
step3Ppm number 1200 ≥ 0 ; ≤ 10000 CO₂ concentration (ppm) between ventilation steps 2 and 3.
stepHysteresisPpm number 50 ≥ 0 ; ≤ 10000 A step changes only above threshold + hysteresis or below threshold − hysteresis (ppm).
step0Pct number 0 ≥ 0 ; ≤ 100 Ventilation control value (%) sent in step 0.
step1Pct number 33 ≥ 0 ; ≤ 100 Ventilation control value (%) sent in step 1.
step2Pct number 66 ≥ 0 ; ≤ 100 Ventilation control value (%) sent in step 2.
step3Pct number 100 ≥ 0 ; ≤ 100 Ventilation control value (%) sent in step 3.
minStepTimeMs integer 0 ≥ 0 A step is kept at least this long before the next change (0 disables it).

#clockMaster/v1

Clock master: sends the time of day (10.001) and the date (11.001) of the simulated clock at a fixed period and after the clock is set.

Ports

Port DPT Channel Role
time 10.001 none day of week and time of the simulated clock
date 11.001 none date of the simulated clock

Device parameters (parameters)

Parameter Type Default Constraints Description
sendPeriodMin integer 1 ≥ 0 ; ≤ 1440 Clock minutes between two broadcasts, aligned on the clock (1 = every full minute); 0 sends only at start and after the clock is set.
sendOnStart boolean true Send time and date shortly after the simulation starts.
startDelayMs integer 1000 ≥ 0 Delay after the simulation starts before time and date are sent.

#timeSwitch/v1

Weekly time switch: sends the programmed value on its output objects at the programmed times of the simulated clock.

Ports

Port DPT Channel Role
output 1.001, 1.002, 1.003, 1.008, 5.001, 5.010, 17.001, 20.102 none object that receives the programmed values

Device parameters (parameters)

Parameter Type Default Constraints Description
program string "" Switching points separated by semicolons: days, time, and value, for example “Mon-Fri 07:00 = 1; Sat,Sun 09:00 = 1; Daily 22:30 = 0”. Days: Mon … Sun, ranges (Mon-Fri), lists (Sat,Sun), or Daily.
sendOnStart boolean true At start, and after the clock is set, send the value of the most recent switching point.

#systemGateway/v1

Gateway to another building system (Modbus, BACnet…): values from that system are entered and sent on KNX; KNX commands are received and forwarded to it, without simulating the other protocol. Uses buttons and inputs.

Ports

Port DPT Channel Role
value any none value read in the other system (temperature, state, meter…), sent on KNX when entered
command any none value received from KNX and forwarded to the other system (mode, setpoint, boost…)

Device parameters (parameters)

Parameter Type Default Constraints Description
system string "Modbus" Name of the system on the other side of the gateway, shown on the device card and in the event log, such as Modbus, BACnet, or M-Bus.

#energyMeter/v1

Energy meter: measures several circuits that other devices switch or that are always supplied; sends their power and integrated energy. Uses buttons and inputs.

Ports

Port DPT Channel Role
power 14.056, 9.024 required power measured on the circuit: W with 14.056, kW with 9.024; a numeric input on this object enters the measured power
energy 13.010, 13.013 required energy counted on the circuit, sent cyclically: Wh with 13.010, kWh with 13.013
totalPower 14.056, 9.024 none sum of the measured circuits: W with 14.056, kW with 9.024

Device parameters (parameters)

Parameter Type Default Constraints Description
meterIntervalMs integer 5000 ≥ 1000 Cyclic sending of power and energy values (ms).
powerSendDeltaW number 10 ≥ 0 Send a power value when it changes by at least this many watts.
energyTimeScale number 60 > 0 Energy counting speed: 60 counts one simulated second as one minute, so that the counter moves visibly; 1 counts real time.

Initial channel state (channels[].initialState)

Parameter Type Default Constraints Description
powerW number 0 ≥ 0 ; ≤ 1000000 Power (W) drawn by the circuit when the simulation starts; a numeric input on the power object changes it.
energyWh number 0 ≥ 0 Energy (Wh) already counted when the simulation starts.

#Equipment

#lamp

Lamp: lit while the relay output is closed. Accepted commands: switch.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
powerW number 60 ≥ 0 ; ≤ 100000 Electrical power (W) drawn while the lamp is on; used by metering actuators. Any switched load can be represented with a matching power.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
on boolean false

#shutter

Roller shutter: receives up/down/stop commands and moves through its actual travel, limited to 0–100%. Accepted commands: motor.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
actualTravelTimeMs (required) integer > 0 Actual time for one complete travel (ms): downwards, and upwards unless actualTravelTimeUpMs is set.
actualTravelTimeUpMs integer > 0 Actual time for one complete upward travel (ms), when it differs from the downward time.
slatTravelMs integer 0 ≥ 0 Venetian blind: time for the slats to turn from open to closed (ms). The motor first turns the slats, then moves the blind. 0 describes a roller shutter without slats.
wiringReversed boolean false Physical wiring with the up and down wires swapped: the motor turns opposite to the command. The actuator's “Inverted wiring” parameter compensates it.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
positionPct number 0 ≥ 0 ; ≤ 100
slatPct number 0 ≥ 0 ; ≤ 100

#dimmableLamp

Dimmable lamp: follows the commanded level with the requested fade; a tunable white lamp also follows the commanded colour temperature. Accepted commands: dim.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
powerW number 40 ≥ 0 ; ≤ 100000 Electrical power (W) at full level; the drawn power is proportional to the level.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
levelPct number 0 ≥ 0 ; ≤ 100

#daliGroup

DALI ballasts in a group: each has a short address (0–63) and follows the commanded level. Accepted commands: dim.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
ballasts integer 2 ≥ 1 ; ≤ 16 Number of ballasts (luminaires) in the group.
firstAddress integer 0 ≥ 0 ; ≤ 63 Short DALI address of the first ballast; subsequent ballasts use consecutive addresses.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
levelPct number 0 ≥ 0 ; ≤ 100
failed integer 0 ≥ 0 ; ≤ 16 Number of ballasts initially reporting a lamp or ballast fault.

#radiator

Radiator with a thermoelectric valve: gradual opening while powered; heat or cooling output is proportional to valve opening. Accepted commands: switch.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
openingTimeMs integer 8000 ≥ 1000 Time for the valve to open fully (ms). Real valves take about 3 minutes; this is compressed like room time and should be short relative to the PWM period.
normallyOpen boolean false Normally open valve: applying power closes it.
powerK number 25 ≥ 1 ; ≤ 60 Temperature difference (K) from outdoors that this radiator can maintain alone with the valve fully open.
emitter string "heating" "heating" (Heating), "cooling" (Cooling) heating warms the room; cooling cools it, for example a fan coil with condensate drainage. Humidity and condensation are not modeled.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
openPct number 0 ≥ 0 ; ≤ 100

#fan

Ventilation fan: runs at the commanded speed (0–100 %) after a short ramp. Accepted commands: dim.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
powerW number 50 ≥ 0 ; ≤ 100000 Electrical power (W) at full speed; the drawn power is proportional to the speed.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
levelPct number 0 ≥ 0 ; ≤ 100

#appliance

Electrical appliance on a switched output (oven, water heater, socket): draws its rated power while powered. Accepted commands: switch.

Parameters (equipment.parameters)

Parameter Type Default Constraints Description
powerW number 2000 ≥ 0 ; ≤ 100000 Electrical power (W) drawn while the appliance is powered.

Initial state (equipment.initialState)

Parameter Type Default Constraints Description
on boolean false